Weil-McLain · Boiler troubleshooting

Check burner flame at high fire and low fire

SlimFit Series 2

What is going on

Judge flame quality through the observation window at both firing rates.

Likely causes

  • Fouled or damaged burner surface
  • Air/fuel imbalance
  • Dirty or obstructed burner

Check in this order

  1. View the flame through the observation window while performing the startup procedure on pages 82 to 85.
  2. High fire flame should be blue and stable, with the burner surface covered in orange dots.
  3. Low fire flame should be stable, spread evenly over the burner surface, and uniform orange in color.
  4. If the flame is poor at high or low fire, perform the testing on page 82. If the problem remains, shut down and let the boiler cool, then remove and clean the burner.
  5. Retest the boiler after cleaning and confirm the flame is acceptable.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.