Weil-McLain · Boiler troubleshooting
Inspect ignition electrode
What is going on
Clean or replace the ignition electrode and check the gap.
Likely causes
- White oxide buildup on electrode
- Worn or damaged electrode insulation
Check in this order
- Remove the ignition electrode from the cover plate (Item 13, p. 153).
- Disconnect the ground wire and ignition cable.
- Discard the ignition electrode gasket.
- Remove white oxides with steel wool. If it cannot be cleaned, replace it.
- Make sure the electrode rods are parallel and the spark gap is 4.5mm.
- Fit a new gasket and reinstall the electrode.
- Use a torque wrench on the two retainer screws. Do not exceed 20 inch-pounds.
- Check the seal of the electrode, igniter gasket and cover plate to prevent gas leaks.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.