Viessmann · Boiler troubleshooting
Replace ignition electrode block
What is going on
Replaces the ignition electrode block and gasket on the burner door.
Check in this order
- Disconnect the ignition cables from the ignition electrodes.
- Remove the two M6 (5 mm hex) screws and washers, then the electrode block from the burner door.
- Remove the gasket.
- Remove the four M12 burner door bolts. Disconnect the gas line and plugs as in the ionization block procedure.
- Fit the new block and gasket.
- Open the burner door and check the electrode-to-electrode and electrode-to-burner dimensions. Adjust if needed.
- Tighten the M12 bolts and M6 screws to the torque in the torque table.
- Reassemble in reverse order.
Applies to: Ignition electrodes
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.