Direct exhaust sidewall termination installation
What is going on
Category IV direct exhaust with the termination through the sidewall. Use only the vent materials and kits listed in Figure 22. Every polypropylene joint needs a locking collar, or vent/air leakage can occur. Use sweep elbows where possible, since short-radius elbows reduce the allowable length. Keep the total vent run within the maximum length in Figure 24.
Likely causes
- Leakage at vent joints if locking collars are missing
- Condensate freezing or vent failure if too much pipe is outside
Check in this order
- Install the vent manufacturer's SlimFit Vent Adapter in the boiler vent outlet, and a reducer if needed.
- Verify the boiler vent/air outlet seal and clamp are installed correctly before inserting the adapter.
- Slope vent piping toward the boiler at least 1/4 in per foot on horizontal runs.
- Support the piping independently of the boiler every 5 ft on horizontal and vertical runs.
- Place a hanger within 6 in of any upturn in the piping.
- Cut the wall hole. For combustible construction, make it at least 3/8 in larger than the vent pipe diameter.
- Install a corrosion-resistant metal thimble in the hole and isolate the pipe per local code.
- Install corrosion-resistant stop plates from the vent pipe manufacturer, with holes just larger than the pipe diameter.
- Insert the last vent length from outside until the female shoulder rests on the outer stop plate.
- Insert the down-turned 90-degree termination elbow into the vent end.
- Install a vent manufacturer bird screen in the open end of the elbow.
- Seal exterior openings thoroughly with exterior caulk.
- For multiple boilers, follow the layout in Figure 28.
Applies to: SlimFit 1000-2000 Series 2 direct exhaust, sidewall
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit-1000-2000 Boiler Manual 550-100-561/1225, p. 33-34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.