Calculate the heating curve slope

Vitotronic 100

What is going on

Slope = (design supply temperature - WWSD temperature) divided by (WWSD temperature - design outdoor temperature). Worked example from the manual: design outdoor 5 F (-15 C), WWSD 70 F (21 C), design supply 160 F (71 C). Slope = (160 - 70) / (70 - 5) = 90 / 65 = 1.4, which is then set on S4 (nearest value on the dial is 1.4 or the next available setting from the table).

Check in this order

  1. Find the design supply temperature and the design outdoor temperature for the building.
  2. Set the WWSD temperature on S5 (factory 70 F / 21 C).
  3. Apply the formula to get the slope.
  4. Set S4 to the matching slope value.

Applies to: Vitotronic 100 KW10B heating curve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B installation manual, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.