Viessmann · Boiler troubleshooting

Connect the condensate drain

Vitocrossal 200 CI2

What is going on

Route the condensate drain so it does not siphon the boiler, and ensure it can drain freely.

Likely causes

  • Drain outlet below the boiler with no pump
  • Drain connected to a shared or siphoning line

Check in this order

  1. Install the condensate drain pipe with a suitable downward slope.
  2. Connect the drain with a P-trap or siphon.
  3. If the boiler condensate outlet is below the drain, install an approved condensing-boiler pump with an overflow switch.
  4. Terminate the drain into an open or vented drain as close to the boiler as possible.
  5. Do not connect other appliance drains, such as a water softener backwash, to this line.
  6. If using a neutralizing unit, discharge through it as required.

Applies to: CI2 399 to 2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 installation instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.