Viessmann · Boiler troubleshooting
Connect the condensate drain
What is going on
Route the condensate drain so it does not siphon the boiler, and ensure it can drain freely.
Likely causes
- Drain outlet below the boiler with no pump
- Drain connected to a shared or siphoning line
Check in this order
- Install the condensate drain pipe with a suitable downward slope.
- Connect the drain with a P-trap or siphon.
- If the boiler condensate outlet is below the drain, install an approved condensing-boiler pump with an overflow switch.
- Terminate the drain into an open or vented drain as close to the boiler as possible.
- Do not connect other appliance drains, such as a water softener backwash, to this line.
- If using a neutralizing unit, discharge through it as required.
Applies to: CI2 399 to 2000
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 installation instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.