Navien · Boiler troubleshooting
Apply propane or high altitude conversion labels
What is going on
After the CO2 or offset values are confirmed, complete and attach the conversion labels next to the rating plate.
Check in this order
- Confirm the CO2 or offset values are within range before labelling.
- Complete the label fields organization name and address, person responsible, kit number, conversion date and gas type.
- Check the kit number on the label matches the installed conversion kit. The label varies by model.
- Place the labels adjacent to the rating plate as shown in Figure 11.
Applies to: NCB700 boilers converted to propane or high altitude
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 145. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.