Weil-McLain · Boiler troubleshooting
Low-temperature system: boiler-bypass piping valve setup
What is going on
Used on converted gravity or radiant systems when primary/secondary piping cannot be applied. Part of the circulator flow is bypassed around the boiler to raise average boiler water temperature and prevent flue gas condensation.
Check in this order
- Start with valve 7a fully closed and valve 7b fully open.
- Slowly open valve 7a while closing valve 7b until gauge 8 reads 60°F higher than gauge 4a.
- If gauge 4a is not installed, set the valves with cold return water, assume 60°F return, and set gauge 8 to at least 120°F.
- Remember valve 7a sets system flow rate and valve 7b sets boiler flow rate.
- The boiler-mounted temperature/pressure gauge can replace a separate gauge 8.
Applies to: CGi-25 to CGi-8 converted gravity or radiant systems (Figures 21 and 22)
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGi Series 5 boiler manual, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.