Zoning with zone valves: two space heating zones (no DHW)
What is going on
Two thermostats on Inputs 2 and 3. Input 1 runs the system circulator through AUX PUMP/OUTPUT.
Check in this order
- Review the 120 VAC output wiring (p. 60) and 24 VAC input wiring (p. 52).
- Wire thermostats to Inputs 2 and 3. Keep both on PRIORITY 2 and choose the space heating system type.
- Assign Input 1 to AUX PUMP/OUTPUT. Select ANY INPUT BY ITS PRIORITY when prompted for activation.
- Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls.
- Do not wire a thermostat to Input 1 (P11-4/5), since it is used for the system circulator.
- Use the factory defaults for the system type, or change if needed.
Applies to: SlimFit Series 3 with zone valves
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.