Weil-McLain · Boiler troubleshooting

Zoning with zone valves: two space heating zones (no DHW)

SlimFit Series 3

What is going on

Two thermostats on Inputs 2 and 3. Input 1 runs the system circulator through AUX PUMP/OUTPUT.

Check in this order

  1. Review the 120 VAC output wiring (p. 60) and 24 VAC input wiring (p. 52).
  2. Wire thermostats to Inputs 2 and 3. Keep both on PRIORITY 2 and choose the space heating system type.
  3. Assign Input 1 to AUX PUMP/OUTPUT. Select ANY INPUT BY ITS PRIORITY when prompted for activation.
  4. Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls.
  5. Do not wire a thermostat to Input 1 (P11-4/5), since it is used for the system circulator.
  6. Use the factory defaults for the system type, or change if needed.

Applies to: SlimFit Series 3 with zone valves

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.