Viessmann · Boiler troubleshooting
Wiring and mounting the wall mount base and remote control
What is going on
Use 2-wire cable, AWG 18 copper. Strip the cable and pull it through the bushing into the wall mount base, then mount the base on an even wall. Watch the cable path while drilling. Connect the two wires to terminals 1 and 2 on the base, and plug the connector into socket 145 on the control unit or on the KM-BUS Expansion Module. Insert the remote control at 90 degrees into the base slot and fold it down until it snaps in. To open it, unlock it from the base with a small screwdriver. Power to the boiler, heating system and external controls must be off during the work.
Check in this order
- Turn off main power to the equipment, heating system and external controls.
- Strip the 2-wire cable (AWG 18 copper) and pull it through the bushing into the wall mount base.
- Mount the wall mount base on an even wall, watching the cable path when drilling.
- Connect the wires to terminals 1 and 2 on the base and plug the connector into socket 145 on the control unit or KM-BUS Expansion Module.
- Insert the remote control at 90 degrees into the base slot, press the top of the housing to seat it, then fold down and snap it in.
- To remove, unlock the remote control from the base with a small screwdriver.
Applies to: Vitotrol 200 remote control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotrol 200 installation instructions, p. 2, p. 5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.