Oil water boiler short cycling
What is going on
Burner turns on and off too often.
Likely causes
- Thermostat in a draft or near a heat source
- Heat anticipator set wrong
- High limit set too low
Check in this order
- Check where the thermostat is mounted inside wall, away from heat and drafts.
- Set the heat anticipator to match the circuit current (see the boiler wiring diagram).
- Raise the limit setting to cut down cycling. Do not go over 220 F.
Applies to: WGO-2 to WGO-9 oil-fired water boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.