Connect a 24 VAC room thermostat through a switching relay
What is going on
A normally open dry contact from a switching relay (T-T) connects to the EA1 module. When the thermostat contact closes, burner operation is load-dependent and the supply water heats to the value in coding address 9b. The contact must be potential-free, since live contacts cause short circuits or phase failure.
Likely causes
- Live voltage on the thermostat contact causes short circuits or phase failure
Check in this order
- Connect the normally open dry contact of the switching relay (T-T) to terminal DE1, DE2 or DE3 of EA1 in the boiler electrical junction box.
- Connect the switching relay to the thermostat and power supply per the manufacturer's instructions.
- Set coding address 3A, 3B or 3C in the General group to 2.
- Confirm the contact is potential-free.
- If only a field-supplied thermostat controls room temperature, the standard and reduced room set points may be set to 37 ºF (3 ºC) to reduce boiler cycling.
Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.