Viessmann · Boiler troubleshooting

Connect a 24 VAC room thermostat through a switching relay

Vitocrossal 300 CU3A

What is going on

A normally open dry contact from a switching relay (T-T) connects to the EA1 module. When the thermostat contact closes, burner operation is load-dependent and the supply water heats to the value in coding address 9b. The contact must be potential-free, since live contacts cause short circuits or phase failure.

Likely causes

  • Live voltage on the thermostat contact causes short circuits or phase failure

Check in this order

  1. Connect the normally open dry contact of the switching relay (T-T) to terminal DE1, DE2 or DE3 of EA1 in the boiler electrical junction box.
  2. Connect the switching relay to the thermostat and power supply per the manufacturer's instructions.
  3. Set coding address 3A, 3B or 3C in the General group to 2.
  4. Confirm the contact is potential-free.
  5. If only a field-supplied thermostat controls room temperature, the standard and reduced room set points may be set to 37 ºF (3 ºC) to reduce boiler cycling.

Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.