Remove boiler from an existing common vent and test the remaining appliances
What is going on
The Ultra boiler cannot be common vented with any other appliance. When an old boiler is replaced, the remaining appliances on the old common vent must be checked to confirm they still vent safely.
Likely causes
- Common vent may be too large for the remaining appliances
- Blocked, leaking, corroded or unpitched vent
- Spillage at the draft hood relief opening
Check in this order
- Visually inspect the existing vent for proper size, horizontal pitch, blockage, restriction, leakage and corrosion.
- Close building doors and windows between the appliance space and other spaces. Turn on clothes dryers, exhaust fans and any non-vented appliances. Run range hoods and bathroom exhausts at maximum. Do not run a summer exhaust fan. Close fireplace dampers.
- Operate the appliance being tested alone, with the other appliances off. Follow its lighting instructions and set the thermostat so it runs continuously.
- After 5 minutes of main burner operation, test the draft hood relief opening for spillage with a match, candle or smoke.
- When each appliance passes, return doors, windows, fans, dampers and other gas appliances to their previous use.
- If the vent does not pass, correct it so it conforms to the National Fuel Gas Code, ANSI Z223.1, or B149.1/B149.2 in Canada. This may mean resizing the vent toward the minimum size from the code tables.
Applies to: Existing common vent systems with appliances left connected after boiler replacement
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.