Weil-McLain · Boiler troubleshooting
Wiring multiple zones with zone valves or circulators
What is going on
Zone valves need their own separate transformer. Zoning with circulators needs one relay per circulator. Do not wire 3-wire zone valves directly to the boiler T-T terminals. Use an isolation relay instead.
Check in this order
- Power zone valves from a separate transformer.
- For circulator zoning, install one relay per circulator as shown in the Wiring Multiple Zones diagram.
- For 3-wire zone valves, connect the valve end switch wires to the isolation relay coil.
- Connect the isolation relay contact across the boiler T-T terminals.
- Do not connect 3-wire zone valves directly to T-T, or boiler damage and unreliable operation can result.
Applies to: CGi Series 5 boilers with multiple zones
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 gas-fired water boiler manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.