Weil-McLain · Boiler troubleshooting

Wiring multiple zones with zone valves or circulators

CGi Series 5

What is going on

Zone valves need their own separate transformer. Zoning with circulators needs one relay per circulator. Do not wire 3-wire zone valves directly to the boiler T-T terminals. Use an isolation relay instead.

Check in this order

  1. Power zone valves from a separate transformer.
  2. For circulator zoning, install one relay per circulator as shown in the Wiring Multiple Zones diagram.
  3. For 3-wire zone valves, connect the valve end switch wires to the isolation relay coil.
  4. Connect the isolation relay contact across the boiler T-T terminals.
  5. Do not connect 3-wire zone valves directly to T-T, or boiler damage and unreliable operation can result.

Applies to: CGi Series 5 boilers with multiple zones

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 gas-fired water boiler manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.