Viessmann · Boiler troubleshooting

Checking static and supply pressure

Vitocrossal 200 CM2

What is going on

Measure gas static pressure and running (supply) pressure at the test nipple. Do not adjust the inlet pressure switch; it is factory set to 4 in. w.c.

Check in this order

  1. Close the gas shut-off valve.
  2. Undo the screw inside test nipple A. Do not remove it.
  3. Connect the pressure tester at test nipple A.
  4. Open the gas shut-off valve.
  5. Check the static pressure (maximum 14 in. w.c.).
  6. Record the value in the Maintenance Record.
  7. Start the burner at maximum output using the emissions test switch.
  8. Measure the supply pressure with a gauge that resolves at least 0.04 in. w.c.
  9. Record the value in the report.
  10. Close the gas shut-off valve.
  11. Remove the pressure tester and close test nipple A.

Applies to: Vitocrossal 200 CM2 186 to 311 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, pp. 14-15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.