Check outdoor temperature sensor

Vitotronic 200-H

What is going on

Test the outdoor sensor resistance and compare it with the actual outdoor temperature.

Likely causes

  • Sensor reads far from actual outdoor temperature
  • Faulty wiring or plug connection

Check in this order

  1. Remove plug and check sensor resistance at terminals 1 and 2.
  2. Compare with the resistance table for the measured temperature.
  3. Disconnect wires from the sensor if values deviate severely from the curve, then repeat the measurement.
  4. Compare with the actual outdoor temperature shown on the display.
  5. Replace the cable or the outdoor sensor depending on the result.
  6. Scan the actual temperature again.

Applies to: Outdoor temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H HK1M installation and service instructions, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.