Zoning four space heating zones with circulators
What is going on
Layout for four space heating zones with no indirect DHW, using circulators or 120VAC zone valves. Shown for 110/155 models; 220-399 use the wiring diagram.
Check in this order
- Review the 120VAC output wiring and the 24VAC input wiring pages (49 and 50) before connecting anything.
- Wire the four thermostat inputs to J17-1/2, J17-4/5, J17-7/8 and J16-1/2.
- Wire each circulator or zone valve to its matching output. Each circulator output is limited to 2.0 A.
- Choose the space heating system type that matches the system, either in the WIZARD setup or manually in the PRIORITY 2 menu under System Settings.
- Keep the factory default settings for the chosen system type, or change them if the system needs it.
Applies to: Evergreen Pro control, four-zone space heating with circulators or 120VAC zone valves
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.