Weil-McLain · Boiler troubleshooting

Zoning four space heating zones with circulators

Evergreen ProSeries 2

What is going on

Layout for four space heating zones with no indirect DHW, using circulators or 120VAC zone valves. Shown for 110/155 models; 220-399 use the wiring diagram.

Check in this order

  1. Review the 120VAC output wiring and the 24VAC input wiring pages (49 and 50) before connecting anything.
  2. Wire the four thermostat inputs to J17-1/2, J17-4/5, J17-7/8 and J16-1/2.
  3. Wire each circulator or zone valve to its matching output. Each circulator output is limited to 2.0 A.
  4. Choose the space heating system type that matches the system, either in the WIZARD setup or manually in the PRIORITY 2 menu under System Settings.
  5. Keep the factory default settings for the chosen system type, or change them if the system needs it.

Applies to: Evergreen Pro control, four-zone space heating with circulators or 120VAC zone valves

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.