Cooling down and draining before servicing the brazed plate heat exchanger
What is going on
Let the brazed plate exchanger cool before opening it, since water inside may still be hot and can cause severe injury.
Check in this order
- Shut off the gas supply at the boiler manual gas valve, but leave power on.
- Run cool domestic water through the boiler by opening a hot fixture. The boiler will lock out on ignition fault, but the internal circulator keeps running to cool components.
- Once components are cool, turn off all electrical power to the boiler.
- Close the domestic cold water inlet isolation valve.
- Release DHW pressure by opening a hot tap downstream of the boiler, then open the DHW drain valves.
- Close the space heating supply and return valves (Boiler Out and Boiler In).
- Release boiler pressure by operating the relief valve or opening the boiler drain, and drain both boiler in and boiler out.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 156. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.