Viessmann · Boiler troubleshooting

Removing an existing boiler from a common vent

Vitorond 200 VD2A

What is going on

Checks to run when an existing boiler is taken out of a shared vent with other gas appliances, so the remaining appliances still vent safely.

Likely causes

  • Common vent is likely oversized once the boiler is removed.

Check in this order

  1. Seal any unused openings in the common venting system.
  2. Inspect the vent for proper size, horizontal pitch, blockage, leakage and corrosion.
  3. Close building doors, windows and doors to other spaces. Run exhaust fans at maximum, but not a summer exhaust fan. Close fireplace dampers to test for negative pressure.
  4. Run the remaining appliance on high fire, with its thermostat set so it runs continuously.
  5. After 5 minutes at high fire, check for spillage at the barometric draft control relief opening with a match, candle or approved tester.
  6. Restore doors, windows, fans, dampers and other appliances to their previous state.
  7. Correct any venting problem so the installation meets the National Fuel Gas Code, ANSI Z223.1. If resizing, use Appendix G tables in that code.

Applies to: Vitorond 200 VD2A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A installation instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.