Removing an existing boiler from a common vent
What is going on
Checks to run when an existing boiler is taken out of a shared vent with other gas appliances, so the remaining appliances still vent safely.
Likely causes
- Common vent is likely oversized once the boiler is removed.
Check in this order
- Seal any unused openings in the common venting system.
- Inspect the vent for proper size, horizontal pitch, blockage, leakage and corrosion.
- Close building doors, windows and doors to other spaces. Run exhaust fans at maximum, but not a summer exhaust fan. Close fireplace dampers to test for negative pressure.
- Run the remaining appliance on high fire, with its thermostat set so it runs continuously.
- After 5 minutes at high fire, check for spillage at the barometric draft control relief opening with a match, candle or approved tester.
- Restore doors, windows, fans, dampers and other appliances to their previous state.
- Correct any venting problem so the installation meets the National Fuel Gas Code, ANSI Z223.1. If resizing, use Appendix G tables in that code.
Applies to: Vitorond 200 VD2A
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A installation instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.