Weil-McLain · Boiler troubleshooting

External limit lockout and automatic restart

SVF Series 1

What is going on

External limits can be wired for manual reset or automatic reset. Manual reset locks the control out and requires a manual reset. Automatic reset restarts the burner after the limit closes.

Likely causes

  • External limit on manual reset circuit (P13 #1 and #2) opened
  • External limit on automatic reset circuit (P13 #3 and #4) opened

Check in this order

  1. Remove the factory jumper before connecting an external limit.
  2. For manual reset, wire isolated limit contacts to P13 #1 and #2.
  3. For automatic reset, wire isolated limit contacts to P13 #3 and #4.
  4. On a manual reset lockout, close the limit and reset the control at the boiler. Cycling power will not clear it.
  5. On automatic reset, the burner restarts 150 seconds after the limit closes.

Applies to: Optional external limit circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.