External limit lockout and automatic restart
What is going on
External limits can be wired for manual reset or automatic reset. Manual reset locks the control out and requires a manual reset. Automatic reset restarts the burner after the limit closes.
Likely causes
- External limit on manual reset circuit (P13 #1 and #2) opened
- External limit on automatic reset circuit (P13 #3 and #4) opened
Check in this order
- Remove the factory jumper before connecting an external limit.
- For manual reset, wire isolated limit contacts to P13 #1 and #2.
- For automatic reset, wire isolated limit contacts to P13 #3 and #4.
- On a manual reset lockout, close the limit and reset the control at the boiler. Cycling power will not clear it.
- On automatic reset, the burner restarts 150 seconds after the limit closes.
Applies to: Optional external limit circuits
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.