Viessmann · Boiler troubleshooting

Participant check (single-boiler system, LON error manager)

Vitotronic 100

What is going on

Checks LON communication between the error manager control unit and the other system units. Only for single-boiler systems with LON.

Check in this order

  1. Confirm the control unit is coded as error manager (coding 79: 1).
  2. Confirm the LON participant number is coded in all control units.
  3. Confirm the participant list is updated in the error manager.
  4. Press the w and OK buttons together for about 2 seconds to enter the participant check.
  5. Select the participant with the up or down button.
  6. Start the check with OK. Arrows stop flashing when communication is verified; if not, the error display appears.
  7. Repeat for further participants.
  8. Press w and OK together for about 1 second to start the check. All 7 arrows show and flash until it finishes; the display and lit buttons of the selected participant flash for about 60 seconds.
  9. Check the LON connection if the check fails.

Applies to: Vitotronic 100 GC1, single-boiler LON systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.