Weil-McLain · Boiler troubleshooting
Connect gas supply piping and leak check
What is going on
Boilers ship set for natural gas only. Install the propane mixer (venturi) and orifice before connecting propane. Pipe dope and leak checks are safety-critical.
Check in this order
- Use two wrenches when tightening gas piping at the boiler, holding the boiler gas connection so it does not turn.
- Install the ½" NPT gas supply and manual shutoff valve per Figure 74. Installer supplies the valve and fittings, including a drip leg (4" nipple) and cap.
- Support the gas piping with hangers, not the boiler or its accessories.
- Use pipe dope compatible with propane, applied sparingly to male threads only.
- Purge all air from the gas supply piping.
- For any pressure test above 14" w.c., disconnect the boiler and cap the gas supply.
- Check all connections for leaks with a bubble test, never an open flame.
Applies to: ECO Tec Series 3 gas connection (Figure 74)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.