Weil-McLain · Boiler troubleshooting
Test ignition system safety device (gas shutoff)
What is going on
Confirms the boiler shuts off gas flow when the main gas supply is cut with the burners on and recovers properly.
Check in this order
- Connect a manometer to the outlet side of the gas valve.
- Start the boiler and let the normal start-up cycle run until the main burners ignite.
- With the main burners on, manually shut off the gas supply at the manual main shutoff gas valve.
- Confirm the burners go off and the manometer shows no gas flow.
- Open the manual main shutoff gas valve.
- Confirm the pilot relights, the flame sensing element senses the pilot flame and the main burners reignite.
Applies to: EG and PEG Series 7 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.