System Layout 3: underfloor circuit with mixing valve and system separation
What is going on
Vitodens 200-W B2HB with DHW storage tank and one underfloor circuit (low-temperature) using a 3-way mixing valve and plate heat exchanger for system separation.
Check in this order
- Install a plate heat exchanger for system separation; required with non-oxygen-diffusion-barrier tubing.
- Make all components on the secondary side of the heat exchanger corrosion-resistant.
- Size field pump P carefully; check boiler supply head pressure drop on page 30.
- Use a low-loss header and boiler pump; Viessmann strongly recommends both.
- Use the accessory kit for a heating circuit with mixing valve.
- Pipe the DHW circulating pump I into the boiler.
Applies to: Vitodens 200-W B2HB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.