Viessmann · Boiler troubleshooting
Check an NTC 10 kΩ sensor (outside, supply, DHW, return)
What is going on
Check a Viessmann NTC 10 kΩ sensor against the resistance curve. The temperature-resistance table values are not legible in the extracted text.
Likely causes
- Sensor reading far from the curve
- Damaged lead or wiring
Check in this order
- Pull the corresponding sensor plug.
- Measure the sensor resistance across terminals 1 and 2 and compare it with the curve.
- If the reading is far off, disconnect the wires from the sensor and repeat the test on the sensor alone.
- Replace the lead if the sensor is good; replace the sensor if it is still off.
- Check the installation if the deviation is severe before replacing the sensor.
Applies to: Outside temperature sensor, supply temperature sensor, DHW tank sensor, return sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H HK1B installation and service instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.