Viessmann · Boiler troubleshooting
Replace fan
What is going on
The fan is removed together with the Venturi pipe and gas valve. Fit the gasket in the correct position.
Check in this order
- Disconnect both connectors from the fan.
- Remove the 6 nuts on the Venturi pipe and remove the Venturi pipe with the fitted gas valve (torque 4.5 lb.ft / 6 Nm when reinstalling).
- Undo the hexagon nuts from the 4 studs.
- Remove the fan, noting how the gasket is positioned.
- Install in reverse order and fit the gasket in the correct position.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.