Viessmann · Boiler troubleshooting
Installing the safety relief valve discharge piping
What is going on
The boiler has an ASME approved 30 psi relief valve. The discharge must not be blocked.
Check in this order
- Do not install any barrier fitting or valve on the outlet of the relief valve.
- Run the copper discharge piping from the relief valve, sized as listed in the manual.
- End the discharge piping within 6 in. of the floor or a floor drain.
- Make sure the discharge piping is not blocked.
Applies to: Vitotron 100 VLN2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotron 100 installation and service instructions, p. 3, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.