Check supply temperature sensor or low-loss header sensor
What is going on
Only one of these sensors may be used.
Likely causes
- Sensor resistance deviates severely from the curve
Check in this order
- Pull plug X3 from the control unit.
- Check resistance across terminals X3.4 and X3.5.
- Compare with the curve (NTC 10 kΩ).
- Replace the sensor if the deviation is severe.
Applies to: Vitodens 200-W B2HA
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.