Viessmann · Boiler troubleshooting

Check supply temperature sensor or low-loss header sensor

Vitodens 200-W B2HA

What is going on

Only one of these sensors may be used.

Likely causes

  • Sensor resistance deviates severely from the curve

Check in this order

  1. Pull plug X3 from the control unit.
  2. Check resistance across terminals X3.4 and X3.5.
  3. Compare with the curve (NTC 10 kΩ).
  4. Replace the sensor if the deviation is severe.

Applies to: Vitodens 200-W B2HA

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.