Viessmann · Boiler troubleshooting

Determine values for a two-stage burner

Vitotronic 100 GC1

What is going on

Measure maximum and basic burner output so the values can be entered in coding 1.

Check in this order

  1. Start up the burner.
  2. Set the override switch to the position shown in the manual.
  3. Determine the maximum burner output from fuel consumption and record the value.
  4. Set the override switch to position a.
  5. Press buttons 9 and the second button together for about 2 seconds to start the relay test.
  6. Activate burner stage 1 ON with the stage button (display shows 4).
  7. Determine the minimum burner output (basic load) from fuel consumption and record the value.
  8. Press the button to complete the relay test.
  9. Enter the recorded values in coding 1 (addresses 08, 09 and 0A) as shown in the table.

Applies to: Vitotronic 100 GC1 with two-stage burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 96. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.