Viessmann · Boiler troubleshooting

Replacing the burner door refractory

Vitocrossal 200 CM2

What is going on

Removes the refractory, rope seal and insulation from the burner door. Refit with the same torque as the burner door.

Check in this order

  1. Loosen the retaining clamp and disconnect the combustion air flex hose; set it aside.
  2. Disconnect the gas line.
  3. Remove the ionization electrode block and the ignition electrode block.
  4. Remove the six M12 (19 mm hex) burner door bolts and washers.
  5. Remove the burner tube (see p. 39). Replace the burner tube gasket if needed.
  6. Remove the rope seal. When refitting, apply high temperature silicone to hold it in place.
  7. Remove the refractory, the electrode block insulation and the insulation blanket.
  8. Reinstall in reverse order. Torque the M12 door bolts to 13 lb.ft (18 Nm).

Applies to: Vitocrossal 200 CM2 186 to 311 burner door

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.