What is going on
Removes the refractory, rope seal and insulation from the burner door. Refit with the same torque as the burner door.
Check in this order
- Loosen the retaining clamp and disconnect the combustion air flex hose; set it aside.
- Disconnect the gas line.
- Remove the ionization electrode block and the ignition electrode block.
- Remove the six M12 (19 mm hex) burner door bolts and washers.
- Remove the burner tube (see p. 39). Replace the burner tube gasket if needed.
- Remove the rope seal. When refitting, apply high temperature silicone to hold it in place.
- Remove the refractory, the electrode block insulation and the insulation blanket.
- Reinstall in reverse order. Torque the M12 door bolts to 13 lb.ft (18 Nm).
Applies to: Vitocrossal 200 CM2 186 to 311 burner door
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.