Viessmann · Boiler troubleshooting
Wire a combustion air damper on a common interface
What is going on
Wire the combustion air damper motor, proving switch and power through the Common Combustion Air Device Interface.
Check in this order
- Disconnect power to the control and the burner.
- Connect the damper motor (120 VAC, 5 FLA max) to the common interface.
- Wire the proving switch rated for 120 VAC.
- Connect the 120 VAC power supply.
- Size the fuse from the damper manual's current rating.
- Provide a disconnect and overcurrent protection as local codes require.
Applies to: Combustion air damper, common interface
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 59. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.