Navien · Boiler troubleshooting

Determine the common vent length

NCB700

What is going on

Total vent length is horizontal width plus vertical height. Use the total BTU/H of all units to read the allowed length from the table.

Check in this order

  1. Add the BTU/H input of every unit in the cascade to get the total BTU/H.
  2. Measure the horizontal width (W) and vertical height (H) of the common vent.
  3. Add W and H to get total length (L = W + H).
  4. Compare the total length with the vent length table for the matching BTU/H load and pipe diameter.
  5. Count each 90° elbow as 8 linear ft (2.4 m) of vent length.

Applies to: NCB700 common vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 Installation & Operation Manual, pp. 93-94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.