Viessmann · Boiler troubleshooting

Water side piping with Hydrostat 3250-Plus control

Vitorond 100

What is going on

This boiler is for closed loop, forced circulation heating systems only. Flush the system before connecting the boiler, since sludge can cause overheating and is not covered under warranty.

Likely causes

  • Sludge left in an older system settling in the boiler

Check in this order

  1. Flush the heating system thoroughly, especially older systems.
  2. Remove the top back panel before connecting pipe fittings to the boiler water supply connection.
  3. Connect the system supply with NPT fittings to the supply connection.
  4. Connect the system return with NPT fittings to the return connection.
  5. Install the temperature and pressure gauge with brass extension coupling in the 1/2 in opening.
  6. Mount the Hydrostat remote sensor kit in a convenient location using the 48 in sensor cable.

Applies to: Vitorond 100 VR1 with Hydrostat 3250-Plus

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.