Viessmann · Boiler troubleshooting
Fixed high limit test simulation #1
What is going on
Tests the fixed high limit by stopping boiler pump flow while the burner is firing. Follow this only where required by law and accept that overheating damage from the test is not covered by Viessmann.
Check in this order
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover from the back of the boiler control to reach the control plugs.
- Enter flue gas test mode from the extended menu.
- Once the burner ignites, unplug the boiler pump plug marked sÖ from the control board, gently with pliers.
- Watch the boiler temperature on the display. The burner should shut off and temperature should continue to rise.
- When the temperature reaches 210°F (99°C), the manual reset high limit trips and shows an F2 fault.
- If the limit is not reached, repeat the test and, two minutes after the burner shuts off, energize the boiler pump for a maximum of 1 second by plugging in the pump plug.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352 (boiler sizes 19 to 100 with flow switches may need the flow switch jumpered)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.