Weil-McLain · Boiler troubleshooting

Combustion air from the boiler room (inside air)

SVF Series 1

What is going on

The SVF can use inside air only when no contaminants are present. Where contaminants are likely, install it as direct vent. The boiler room needs openings sized for all appliances and exhaust fans in the room. The boiler room must never be under negative pressure unless every appliance is direct vent.

Likely causes

  • Negative pressure in the boiler room from exhaust fans or mechanical ventilation
  • Louvers or grilles reducing free area
  • Tight construction stopping outside air from reaching the room

Check in this order

  1. Confirm no contaminants are present in the boiler room before using inside air.
  2. If contaminants are likely, install the boiler as direct vent.
  3. Size the air openings for all appliances and air movers using the room air, not just the boiler.
  4. Use Figure 26 on page 33 for opening sizes based on the installation conditions.
  5. Reduce the free area of openings for any louver or grille.
  6. In tight construction, provide air openings from outside sized per Figure 26.
  7. Do not let exhaust fans or air movers pull the boiler room under negative pressure.
  8. The damper or louver control can supply 120V to a damper and take a closure switch input to prove the damper is open.

Applies to: Direct exhaust combustion air from boiler room

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 Boiler Manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.