Lower the fixed high limit to 212 ºF / 100 ºC
What is going on
Field adjustment of the fixed high limit. Remove power first. Adjustment is permanent.
Check in this order
- Remove the fuse.
- Unclip the cover at the four snap-in clips and remove it.
- Pull the front panel behind the cover upward and swing it open to the rear.
- Turn the slotted screw on the rear of the fixed high limit to 212 ºF / 100 ºC.
- Refit the front panel, cover and fuse.
- Check the box in the Vitotronic 300 service instructions to confirm the adjustment.
Applies to: Vitotronic 300 fixed high limit (Etheco/EGO)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 installation instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.