Viessmann · Boiler troubleshooting

Lower the fixed high limit to 212 ºF / 100 ºC

Vitotronic 300

What is going on

Field adjustment of the fixed high limit. Remove power first. Adjustment is permanent.

Check in this order

  1. Remove the fuse.
  2. Unclip the cover at the four snap-in clips and remove it.
  3. Pull the front panel behind the cover upward and swing it open to the rear.
  4. Turn the slotted screw on the rear of the fixed high limit to 212 ºF / 100 ºC.
  5. Refit the front panel, cover and fuse.
  6. Check the box in the Vitotronic 300 service instructions to confirm the adjustment.

Applies to: Vitotronic 300 fixed high limit (Etheco/EGO)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.