Viessmann · Boiler troubleshooting

Clean the condensate trap and drain pipe

Vitocrossal 200 CI2

What is going on

Clean at least once a year.

Check in this order

  1. Disconnect the condensate drain pipe to the neutralizing system from the condensate trap.
  2. Unscrew the lower part of the condensate trap, remove the float and clear deposits.
  3. Clean all components.
  4. Reassemble the condensate trap and refit the drain pipe.
  5. If needed, clean the neutralizing system per its instructions.
  6. Make sure the hose does not sag; support it if needed.
  7. Check that condensate drains freely and operate the boiler only with the condensate trap fitted.

Applies to: Vitocrossal 200 CI2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.