Weil-McLain · Boiler troubleshooting

Annual startup: check water system and cold fill pressure

SlimFit Series 2

What is going on

Check that the water system is correct and that pressure stays within limits while the boiler heats.

Likely causes

  • Expansion tank undersized or not performing
  • Air trapped in system
  • Incorrect cold fill pressure

Check in this order

  1. Confirm all system components are installed correctly and working.
  2. Check cold fill pressure. It should be about 12 psig.
  3. Watch system pressure while the boiler heats. Excess rise points to expansion tank sizing or performance.
  4. Remove air vent caps and briefly press the push valve to flush each automatic air vent. Reinstall the caps.
  5. Check that vents do not leak and replace any that do.
  6. Check system water chemistry (inhibitor concentration, pH and hardness). See page 79 of the manual.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.