Weil-McLain · Boiler troubleshooting
Annual startup: check water system and cold fill pressure
What is going on
Check that the water system is correct and that pressure stays within limits while the boiler heats.
Likely causes
- Expansion tank undersized or not performing
- Air trapped in system
- Incorrect cold fill pressure
Check in this order
- Confirm all system components are installed correctly and working.
- Check cold fill pressure. It should be about 12 psig.
- Watch system pressure while the boiler heats. Excess rise points to expansion tank sizing or performance.
- Remove air vent caps and briefly press the push valve to flush each automatic air vent. Reinstall the caps.
- Check that vents do not leak and replace any that do.
- Check system water chemistry (inhibitor concentration, pH and hardness). See page 79 of the manual.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.