Annual start-up checklist
What is going on
Service technician annual start-up for Ultra Series 4 boilers. Start-up checkout continues at Startup, fill the system (p. 35).
Check in this order
- Address any problems reported by the owner first.
- Shut off power before any service work.
- Check the boiler area for combustibles, gasoline and flammable vapors.
- Check the air intake area for contaminants and remove them.
- Remove the jacket front door and inspect the interior. Check door gaskets and replace any damaged gasket.
- Clean the venturi air inlet silencer if needed and replace it.
- Vacuum sediment from inside the boiler. Clear obstructions.
- Do not use solvents on any boiler component.
- Clean the condensate trap, check condensate lines, and refill the trap with fresh water.
- Check all water and gas piping for leaks. Check gas line per page 29.
- Verify combustion and ventilation air openings are clear. Check automatic dampers if used.
- Visually inspect flue venting and air piping for blockage, deterioration or leaks. Make sure the air inlet hose is sealed if used.
- Check cold fill pressure (usually about 12 psig) and watch pressure rise while the boiler heats up.
- Inspect automatic air vents and air separators. Flush vents, replace any that leak.
- Check water chemistry (pH, hardness, inhibitor level).
- Check the expansion tank (see expansion tank guide).
- Inspect and clean the ignition electrode (see ignition guide).
- Check ignition and ground wiring and all boiler wiring.
- Check control settings in U-Control and external limit controls.
- Start the boiler and complete the checks and tests in this manual, then complete the check-out on p. 42.
- Check flame inspection and flame signal (see flame guide).
- Clean the Nanogate heat exchanger if flue temperature is more than 54°F above return water temperature.
- Inspect jacket front door gaskets and replace if needed.
- If combustion or performance indicates, clean heat exchanger (p. 126) and clean burner with compressed air only. Vacuum the blower.
- Review results with the owner and fill out the Installation and Service Certificate.
Applies to: Ultra Series 4 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 108-110. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.