Weil-McLain · Boiler troubleshooting

Annual start-up checklist

Ultra Series 4

What is going on

Service technician annual start-up for Ultra Series 4 boilers. Start-up checkout continues at Startup, fill the system (p. 35).

Check in this order

  1. Address any problems reported by the owner first.
  2. Shut off power before any service work.
  3. Check the boiler area for combustibles, gasoline and flammable vapors.
  4. Check the air intake area for contaminants and remove them.
  5. Remove the jacket front door and inspect the interior. Check door gaskets and replace any damaged gasket.
  6. Clean the venturi air inlet silencer if needed and replace it.
  7. Vacuum sediment from inside the boiler. Clear obstructions.
  8. Do not use solvents on any boiler component.
  9. Clean the condensate trap, check condensate lines, and refill the trap with fresh water.
  10. Check all water and gas piping for leaks. Check gas line per page 29.
  11. Verify combustion and ventilation air openings are clear. Check automatic dampers if used.
  12. Visually inspect flue venting and air piping for blockage, deterioration or leaks. Make sure the air inlet hose is sealed if used.
  13. Check cold fill pressure (usually about 12 psig) and watch pressure rise while the boiler heats up.
  14. Inspect automatic air vents and air separators. Flush vents, replace any that leak.
  15. Check water chemistry (pH, hardness, inhibitor level).
  16. Check the expansion tank (see expansion tank guide).
  17. Inspect and clean the ignition electrode (see ignition guide).
  18. Check ignition and ground wiring and all boiler wiring.
  19. Check control settings in U-Control and external limit controls.
  20. Start the boiler and complete the checks and tests in this manual, then complete the check-out on p. 42.
  21. Check flame inspection and flame signal (see flame guide).
  22. Clean the Nanogate heat exchanger if flue temperature is more than 54°F above return water temperature.
  23. Inspect jacket front door gaskets and replace if needed.
  24. If combustion or performance indicates, clean heat exchanger (p. 126) and clean burner with compressed air only. Vacuum the blower.
  25. Review results with the owner and fill out the Installation and Service Certificate.

Applies to: Ultra Series 4 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 108-110. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.