Weil-McLain · Boiler troubleshooting

Set up 0-10 VDC remote modulation from an external controller

SlimFit Series 3

What is going on

Uses an external controller's 0-10 VDC signal to set boiler modulation. Single boiler only.

Check in this order

  1. Wire the external controller signal to P15 pin 6 (positive) and pin 5 (common).
  2. Use PRIORITY 1 for DHW if needed. Connect the DHW aquastat to INPUT 2 or INPUT 3 and assign that input to PRIORITY 1.
  3. Use PRIORITY 2 for the system being modulated. Assign INPUT 1 to PRIORITY 2 and accept the Wizard defaults for INPUT 1.
  4. After the Wizard, open the ASSIGN INPUTS menu for INPUT 1 and change SOURCE from TT1 to 0-10V.
  5. Check that the heat demand starts at 0.9 VDC and stops at 0.8 VDC.
  6. Confirm OUTPUT 1 (120 VAC) switches with the heat demand. It is a good output for the system pump.

Applies to: Single SF-550 or SF-750 boiler, not networked

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 57. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.