Set up 0-10 VDC remote modulation from an external controller
What is going on
Uses an external controller's 0-10 VDC signal to set boiler modulation. Single boiler only.
Check in this order
- Wire the external controller signal to P15 pin 6 (positive) and pin 5 (common).
- Use PRIORITY 1 for DHW if needed. Connect the DHW aquastat to INPUT 2 or INPUT 3 and assign that input to PRIORITY 1.
- Use PRIORITY 2 for the system being modulated. Assign INPUT 1 to PRIORITY 2 and accept the Wizard defaults for INPUT 1.
- After the Wizard, open the ASSIGN INPUTS menu for INPUT 1 and change SOURCE from TT1 to 0-10V.
- Check that the heat demand starts at 0.9 VDC and stops at 0.8 VDC.
- Confirm OUTPUT 1 (120 VAC) switches with the heat demand. It is a good output for the system pump.
Applies to: Single SF-550 or SF-750 boiler, not networked
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.