Weil-McLain · Boiler troubleshooting

Zone valve and multiple zone wiring

EG / PEG Series 7

What is going on

Zone valves need their own transformer. Zoning with circulators needs a relay for each circulator. Never connect 3-wire zone valves directly to the boiler T-T terminals; that can damage boiler components or cause unreliable operation.

Likely causes

  • 3-wire zone valves wired directly to the T-T terminals

Check in this order

  1. Power zone valves from a separate transformer.
  2. For zoning with circulators, install one relay per circulator as shown in Figure 31.
  3. For 3-wire zone valves, install an isolation relay.
  4. Connect the zone valve end switch wires to the isolation relay coil.
  5. Connect the isolation relay contact across the boiler T-T terminals.
  6. Refer to the zone valve maker's literature for application and wiring details.

Applies to: EG water boilers with multiple zones

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.