Rinnai · Boiler troubleshooting
Central heating works, no domestic hot water
What is going on
Heating runs but no DHW.
Likely causes
- DHW program key not on
- Flow switch not working
- T3 DHW sensor in plate heat exchanger defective
- RS100 timer or DHW program not responding
- Three-way valve not moving to DHW
Check in this order
- Switch the DHW program on at the Control Tower.
- Check the flow switch for impurities and operation; replace if needed.
- Replace the T3 DHW sensor if defective.
- If using an RS100, check its DHW timer times and see its instructions.
- Check three-way valve wiring; replace the valve motor if needed.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.