Rinnai · Boiler troubleshooting

Central heating works, no domestic hot water

What is going on

On the Rinnai E50CRN, E75CRN, E75CRP, E110CRN and E110CRP boilers, central heating runs but there is no domestic hot water. Start with the settings and the simple parts before touching wiring. Gas and electrical repairs on the boiler should be done by a qualified technician with power isolated.

Likely causes

  • DHW program key not switched on
  • Flow switch not working
  • T3 DHW sensor in the plate heat exchanger defective
  • RS100 timer or DHW program not responding
  • Three-way valve not moving to the DHW position

Check in this order

  1. Switch the DHW program on at the Control Tower.
  2. Check the flow switch for impurities and operation; replace if needed.
  3. Replace the T3 DHW sensor if defective.
  4. If using an RS100, check its DHW timer times and see its instructions.
  5. Check three-way valve wiring with power off; replace the valve motor if needed.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.