Weil-McLain · Boiler troubleshooting

Check the limit control and extra high limit (oil water boiler)

Weil-McLain WGO Series 4

What is going on

How to prove the limit stops the burner, and how the optional second high limit is set.

Check in this order

  1. With the burner running, turn the limit setting below the actual boiler water temperature. The burner must stop and the circulator keeps running.
  2. Turn the setting back above the water temperature. The burner should relight.
  3. If a second high limit is required (ASME, UL 726 or Canadian rules), it goes in the supply piping between the boiler and the isolation valve.
  4. Set that second limit at least 20 F above the combination control set point. Max allowed setting is 220 F.
  5. The combination control must run with thermal pre-purge or thermal targeting on, unless the boiler falls under one of the exemptions printed in the manual.

Applies to: WGO-2 to WGO-9 oil-fired water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, High temperature limit p.23; Check-out procedure p.28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.