Check boiler water, DHW or flow temperature sensor
What is going on
Sensors are NTC 10 kΩ. Compare measured resistance with the curve and replace the sensor if the deviation is severe.
Likely causes
- Sensor resistance deviates severely from curve
- Sensor cable damaged
Check in this order
- Drain the boiler before replacing the boiler temperature sensor (scalding risk).
- Boiler water sensor remove lead to boiler water temperature sensor and check resistance.
- DHW tank sensor pull plug from the cable harness at the control unit and check resistance.
- Supply or low-loss header sensor pull plug X3 from the control unit and check resistance across terminals X3.4 and X3.5. Only one such sensor may be used.
- Replace the sensor if the deviation is severe.
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 19, 28, 35 service instructions, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.