Weil-McLain · Boiler troubleshooting
Final checks before starting the boiler
What is going on
Complete these checks before the first firing. Gas and venting faults can cause severe injury or death.
Check in this order
- Read the control setup instructions and confirm all settings are correct.
- Confirm the boiler and system are full of water and components are set for operation.
- Vent air from the system with the manual vents, then check piping for leaks.
- Fill the condensate trap with water.
- Check that electrical connections are correct and tight.
- Inspect vent and air piping for corrosion, damage or sagging, and confirm it is installed per the manual.
- Confirm the venting is gas-tight to prevent flue gas spillage and carbon monoxide.
- Use a leak detector or smell near the floor and around the boiler for gas odor before and during first operation. Do not start if there is any gas leak.
Applies to: Pre-startup checks
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.