Calibrate the burner with combustion analysis
What is going on
Measure at the final site with calibrated equipment and adjust the burner to local conditions.
Likely causes
- Weather
- Length of horizontal vent pipe
- Chimney diameter and height
- Side wall (power) venting
- Altitude
- Oil quality and heating value
- Other fuel appliances running at the same time
Check in this order
- Use calibrated combustion equipment at the final installation site.
- Take CO2, stack temperature, draft and CO readings in the flue pipe between the boiler and the barometric draft regulator, before dilution air.
- Measure overfire draft at the combustion chamber observation port opening.
- Adjust the burner until results are acceptable for the local conditions.
- Refer to the burner technical table on page 41 or 42 of the manual for burner data.
- Refer to the Beckett or Riello burner instructions for burner settings.
Applies to: VR1 40 to 63, 161 to 245 with #2 oil
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.