Zone pump system wiring (up to 3 zones)
What is going on
Wiring for a zone pump system with up to 3 zones using dry contact or thermostat connections.
Check in this order
- Wire each zone pump (max. 2.5 A) to its thermostat zone, with line and neutral.
- Wire the boiler external pump and boiler internal pump (max. 2.5 A each).
- For a 24 V thermostat, connect it to the R and C terminals on the boiler PCB.
- Use the C terminals only for 24 V thermostats that have a COMMON wire.
- Dry contact connections have no 24 VAC power.
Applies to: NCB700 zone pump systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.