Viessmann · Boiler troubleshooting
Clock the natural gas meter to verify input
What is going on
Time the meter to check the boiler gas input. Only use this method at low altitude. Get the heating value from the gas supplier before timing.
Likely causes
- Gas input too high or too low
Check in this order
- Turn off all other gas appliances served by the meter.
- Time how many seconds the boiler takes to use 10 ft³ of gas.
- Multiply 3600 by 10, then divide by the seconds measured.
- Multiply that result by the gas heating value in Btu per ft³ (or use the nominal 1000 Btu/ft³ if the supplier value is not available).
- Compare the result to the boiler input rating.
- A boiler underfired by up to 5% is acceptable. Do not overfire the boiler.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.