Viessmann · Boiler troubleshooting
Inspect and replace burner mesh assembly and refractory
What is going on
Replace the burner mesh assembly if the wire mesh is damaged.
Likely causes
- Damaged wire mesh
- Damaged refractory
Check in this order
- Remove electrodes A.
- Remove the four nuts D and take off the fan with gas valve C.
- Remove the three nuts B and take off the burner mesh assembly H.
- Remove refractory F with thermal insulating mat E.
- Remove old burner mesh gasket G.
- Check refractory F and replace if damaged.
- Fit thermal insulating mat E and refractory F per electrode position, using the positioning aid.
- Fit new burner mesh assembly H with new gasket G and secure with three nuts.
- Fit the fan with gas valve.
- Do not damage the burner head wire gauze.
Applies to: Vitocrossal 300 CU3A burner head
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.