Viessmann · Boiler troubleshooting

Inspect and replace burner mesh assembly and refractory

Vitocrossal 300 CU3A

What is going on

Replace the burner mesh assembly if the wire mesh is damaged.

Likely causes

  • Damaged wire mesh
  • Damaged refractory

Check in this order

  1. Remove electrodes A.
  2. Remove the four nuts D and take off the fan with gas valve C.
  3. Remove the three nuts B and take off the burner mesh assembly H.
  4. Remove refractory F with thermal insulating mat E.
  5. Remove old burner mesh gasket G.
  6. Check refractory F and replace if damaged.
  7. Fit thermal insulating mat E and refractory F per electrode position, using the positioning aid.
  8. Fit new burner mesh assembly H with new gasket G and secure with three nuts.
  9. Fit the fan with gas valve.
  10. Do not damage the burner head wire gauze.

Applies to: Vitocrossal 300 CU3A burner head

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.