Weil-McLain · Boiler troubleshooting

Air vent and fill valve placement

CGi Series 5

What is going on

Do not use an automatic air vent with a closed-type expansion tank, because it lets air out and waterlogs the tank. The fill valve must always connect to the expansion tank, wherever the tank, circulator or air separator is located.

Likely causes

  • Automatic air vent used with closed-type expansion tank (waterlogs tank)
  • Fill valve not connected to expansion tank

Check in this order

  1. With a diaphragm or bladder tank, install an automatic air vent.
  2. With a closed-type tank, do not install an automatic air vent.
  3. Connect the fill valve to the expansion tank, regardless of tank, circulator or air separator location.
  4. For a closed-type tank, pipe from the top of the air separator to the tank fitting (Figure 16).

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.